VTB-TM 24 Volt 32 Tone Combi Interrupt I.S. 3218:2013


The new revision of Irish Standard IS3218-2014 now specifies that in buildings which are not permanently manned, any external sounder shall automatically silence after a period of 15 minutes, leaving any visual indicator associated with the entrance, or acting as guidance to the location of the control panel to continue to operate. With this in mind, the VTB Combi Interrupt has been designed with all the standard VTB features with the added capability of a 15 minute time out on the sounder, fully complying with the updated standard.


  • IP65
  • 88dB, 103dB, 109dB
  • 11mA, 19mA, 37mA




VTG Spatial Sounder 24Vdc EN54-3 Approved


The VTG family of sounders has been designed to cover a wide spectrum of applications. The 24 volt EN54-3 approved version is for use with conventional fire alarm systems including two wire (SAV-WIRE®) and as standard comes with 32 tones. The sounder is supplied with a two stage alarm override which is activated by a third negative wire from the fire panel.

All tones have been selected to comply with the latest sound patterns and frequencies used throughout the world. All tone options are fully synchronised. The sounder function has been fully approved to EN54-3 by the LPCB and VdS on tones 1, 8, 11, 25 and 27.

Features


  • Fully approved to EN54-3 by LPCB and VdS
  • 32 tones plus a selectable override tone
  • Shallow base IP21C and deep base IP33C versions available
  • Designed to work with both conventional and two-wire (SAV-WIRE®) systems
  • Unique twist and lock bayonet mounting system
  • Removable cover on deep base for surface wiring
  • Features base locking system as standard

VTB Spatial Sounder/Beacon EN54-3 Approved 24Vdc


​The VTB 24Vdc sounder beacon is part of the VTG family of products designed for use with conventional fire alarm systems including two wire (SAV-WIRE®) and other general 24Vdc applications. The sounder function, like all VTG products, comes as standard with 32 tones. The beacon function has been designed for maximum all-round visibility, coupled with low power consumption utilising an array of energy efficient LEDs. The sounder function features a two-stage alarm override which is activated by a third negative wire from the fire panel. Both the sounder and beacon functions are fully synchronised. The product can also be used as a beacon only which is easily selected by a DIL switch at the time of installation.

Features


  • 32 tones plus a selectable override tone
  • Shallow base IP43 and deep base IP65 versions available
  • Switch selectable beacon only feature
  • Unique twist and lock bayonet mounting system
  • Removable cover on deep base for surface wiring
  • Features base locking system as standard

CWS100-AV Conventional Wall Sounder Beacon


​The CWS100-AV conventional wall sounder beacon forms the core of our EN54-23 Visual Alarm Device range. The unit is of a modular design and is weatherproof as standard, therefore the unit can be used either standalone or with the addition of an addressable module (ALWS-MOD). This modular approach means the majority of site applications can be achieved with just a few core stock components. When used with either of the intelligent module options the unit has a built in microphone which allows the unit to indicate a fault should the sounder not operate when activated.


  • Flexible modular design
  • Third party approved to the requirements of EN54-3 and EN54-23
  • 32 Tone Settings
  • Two stage alarm capability
  • Weatherproof as standard
  • Easy to install
  • Silent sounders setting for beacon only use
  • Microphone self test facility
  • Robust & High reliability
  • IP65
CWS100-AV EN54-3 & EN54-23 Compliant

Alarm Devices